| MODEL | EA906PS | EA906PH | EA9010PS | EA9010PH |
| Capacity | 6 KVA / 5400 W | 10 KVA / 9000 W | ||
| INPUT | ||||
| Rated voltage | 208 V / 220 V / 230 V / 240 Vac | |||
| Voltage range | 110 ~ 160 Vac (linear derating between 50% and 100% load); 160 ~ 280 Vac (no derating); 280 ~ 300 Vac (derating 50%) |
|||
| Rated frequency | 50 / 60 Hz (auto-sense) | |||
| Frequency range | 40 ~ 70 Hz | |||
| Power factor | ≥ 0.99 | |||
| Total harmonic distortion (THDI) | ≤ 5% | |||
| Bypass voltage range | - 40% ~ + 15% (settable) | |||
| OUTPUT | ||||
| Voltage | 208 V / 220 V / 230 V / 240 Vac (settable) | |||
| Voltage regulation | ± 1% | |||
| Frequency | 45 ~ 55 Hz or 55 ~ 65 Hz (synchronized range); 50 / 60 Hz ± 0.1 Hz (battery mode) | |||
| Waveform | Pure sine wave | |||
| Crest factor | 3:1 | |||
| Total harmonic distortion (THDV) | ≤ 2% (linear load); ≤ 5% (non-linear load) | |||
| Transfer time | Mains mode to battery mode: 0 ms; Inverter mode to bypass mode: 0 ms | |||
| Inverter overload capability | 102% ~ 125%: Transfer to bypass in 10 mins; 125% ~ 150%: Transfer to bypass in 1 min; > 150%: Transfer to bypass in 0.5 s |
|||
| Bypass overload capability | 102% ~ 125%: Shut down in 20 mins; 125% ~ 150%: Shut down in 2 mins; > 150%: Shut down in 1 s |
|||
| BATTERIES | ||||
| DC voltage | 192 VDC (168 / 180 / 192 / 204 / 216 / 228 / 240 VDC optional) | |||
| Inbuilt battery | 16×7 Ah | / | 16× 9 Ah | / |
| Recharge time | Standard model (S): 90% capacity restored in 4 hours; Long time model (H): depend on the capacity of battery |
|||
| SYSTEM | ||||
| EFFICIENCY | ≥ 93%, ECO mode 98% | |||
| Display | LCD+LED | |||
| Alarms | Battery mode, battery voltage low, fans fault etc. | |||
| Maximum Parallel numbers | 6 | |||
| EMI | IEC/EN62040-2 | |||
| EMS | IEC 61000-4-2 (ESD) | |||
| IEC 61000-4-3 (RS) | ||||
| IEC 61000-4-4 (EFT) | ||||
| IEC 61000-4-5 (Surge) | ||||
| COMMUNICATIONS | ||||
| RS232 / USB / RS485 / dry contacts | Supports Windows 98 / 2000 / 2003 / XP / Vista / 2008 / 7 / 8 / 10 | |||
| SNMP | Power management from SNMP manager and web browser | |||
| OTHERS | ||||
| Humidity | 20 ~ 90% RH @ 0 ~ 40℃ (non-condensing) | |||
| Noise level | ≤ 55 dB (1m) | |||
| Dimensions (W×D×H) (mm) | 191×462×710 | 191×462×350 | 191×462×710 | 191×462×350 |
| Packaged dimensions (W*D*H) (mm) | 308×640×896 | 267×573×436 | 308×640×896 | 267×573×436 |
| Net weight (kg) | 58.7 | 15.6 | 67.2 | 16.1 |